|
Parameters and Setpoints ASIC/1-8655 |
|
|
|
Active Control Mode |
|
Shows present mode of the controller. |
|
Active Cooling Temperature Setpoint |
|
The current cooling temperature setpoint saved in RAM |
|
Active Demand Group |
|
Present Demand Group as received on the communication line. |
|
Active Demand Level |
|
Present Demand Level as received on the communication line. |
|
Active Heating Temperature Setpoint |
|
The current heating temperature setpoint saved in RAM. |
|
Afterhours Date Stamp |
|
Holds a month, date and hour which the user should set to the current date and hour when he resets Afterhours Total Time to zero. [XX/XX XX am/PM]. User changeable. |
|
Afterhours Enable |
|
If set to [Yes] the push-button on input 2 on the wall sensor activates the Afterhours Override mode upon being depressed. When this is enabled the push-button will give override to occupied mode, or toggle the lights if already in occupied [Yes, No Default No]. User-changeable. |
|
Afterhours Request |
|
Tells whether the controller is currently operating in Afterhours Override mode. [Yes or No]. Not user-changeable. |
|
Afterhours Reset |
|
Action to clear Afterhours Total Time and update Afterhours Date. |
|
Afterhours Status |
|
Tells whether the Afterhours button has been pressed and Afterhours time allowed is non-zero. [Yes or No]. |
|
Afterhours Time Allowed |
|
This is an non-volatile memory variable that represents the number of minutes the After Hours Override will be in effect when the push button is pressed. The time period that Afterhours Override will be in effect following a triggering by the wall sensor pushbutton. This is used only during Night Setback or in an Unoccupied State. Default 60 minutes Range 0-255 minutes Resolution 1 minute [0 to 255 minutes]. |
|
Afterhours Time Remaining |
|
The number of minutes remaining before Afterhours Override mode will cease to operate and the control will revert to its original state. [0 to 255 mins]. Not user-changeable. |
|
Afterhours Total Time |
|
The accumulated time the controller has spent in Afterhours Override mode. The user must set this counter to 0 and appropriately change the Afterhours Date Stamp if he or she wished to begin a new tracking of the time spent in Afterhours Override mode. [0 to 65535 mins, Default 0 mins]. |
|
Alarm 1, Zone Temperature Alarm |
|
This alarm is set in all control states, bit 0 = 1 zone temperature too hot; bit 1 = 1 zone temperature too cold, in A1_Alarm1ZoneTemp |
|
Alarm 2, Discharge Air Temperature Alarm |
|
If the discharge air temperature raises above the DAT High Limit Setpoint, a high DAT high limit alarm is set. If the setpoint is 0, this alarm is ignored. If the discharge air temperature falls below the DAT Low Limit Setpoint .a DAT Low Limit alarm is set. Once a discharge air alarm is set, the temperature must recover by the DAT Alarm Hysteresis before the alarm is cleared. . bit 2 = 1 too hot; bit 3 = 1 too cold. |
|
Alarm 3, Water Loop Temperature |
|
If the water loop temperature raises above the Water Loop Max Alarm Setpoint this point a high water loop alarm is set. If the setpoint is 0, this alarm is ignored. If the water loop temperature falls below Water Loop Min Alarm Setpoint , a low water loop alarm is set. . Once a water loop alarm is set, the temperature must recover by the Water Loop Alarm Hysteresis before the alarm is cleared. bit 4 = 1 Hi ; ,bit 5 = 1, |
|
Alarm 4 HI, Compressor Lockout |
|
If Fault Compressor Lockout is set, the compressor will turn off on Compressor Fault. It will wait for a Compressor Retry Wait time and then try again. If another Compressor Fault Alarm occurs before the end of the minimum ON time, another attempt is made to Start the compressor, as described above, until the maximum allowed tries has been exceeded. If Fault Compressor Lockout is Enabled, when the maximum allowed tries [Default, 3] has been reached, then a Compressor Lockout Alarm is set and no further attempt is made to start the compressor. The Compressor Lockout Alarm is cleared by only a new MT=10, M1=14 message, or resetting power to the unit. |
|
Alarm 4 LO, Compressor Fault |
|
When the compressor 1 or 2 is ON and when Compressor Fault Enable, is yes, the status of the Compressor Fault contacts across input 6 are monitored. If a Low Input 6 Fault is detected for a Compressor Fault Delay [Default 20 s], then the Alarm 4, LO Compressor Fault is set. |
|
Alarm 5 - Proof of Fan Alarm |
|
Proof of Fan Alarm, Table 16, Entry 2, bit 0 (Alarm 5 HI) is set when proof of fan fails. |
|
Analog Output Assignment |
|
Identifies the value used to control the analog output: 0 - None Not assigned. 1 - PA_CLGRequirement ; 2 - PA_HTGRequirement ; 3 - PA_EconoCoolReq , 4- Changeover HTG/CLG. |
|
Analog Output Calibrate |
|
Calibration factor for 10 Vdc Analog Outputs. May be adjusted if Analog output reads high or low. |
|
Analog Output Max Output |
|
The voltage 0..255 = 0..10 Vdc when the control input is 100% (255). |
|
Analog Output Min Output |
|
The voltage 0..255 = 0..10 Vdc when the control input is 0% (0) |
|
Analog Output Value |
|
The actual output value 0..255 = 0..10 Vdc. |
|
ASIC/1 Day "Day of Week" |
|
The day of the week as the controller knows it. The clock may be synchronized to the current day, date and time as the PC knows them by placing the cursor at the screen location for this parameter and pressing <s>. The day may be set to holiday by placing the cursor at the screen location and pressing <h>. The holiday status may only be cleared by a re-synchronization of the controller. These are the only two methods by which the clock may be changed. NOTE: If the controller clock reads "NA" for the day, this indicates that the controller has not been synchronized. [1 = Monday]. |
|
ASIC/1 Time "Time of Day" |
|
The time of day as the controller knows it. The clock may be synchronized to the current day, date and time as the PC knows them by placing the cursor at the screen location for this parameter and pressing <s>. The day may be set to holiday by placing the cursor at the screen location and pressing <h>. The holiday status may only be cleared by a resynchronization of the controller. These are the only two methods by which the clock may be changed. [ XX:XX:XX]. |
|
Auxiliary 1,2 Output Mask |
|
Auxiliary outputs may be assigned which are not connected to the sequence of operation. They may be controlled only by overrides from a user interface. |
|
A1_Auxiliary1OutputMask, A1_Auxiliary2OutputMask. |
|
Auxiliary Cooling Enable |
|
Enables Auxiliary Cooling Feature which will bring on an additional output if the Cooling Requirement is equal to 100%(255) and the Zone Temperature is greater than the Active Cooling Setpoint by a value greater than the Auxiliary Cooling Temperature Offset for an Auxiliary Cooling Wait Time . |
|
Auxiliary Cooling Output Mask |
|
Assigns output mask if Auxiliary Cooling has been enabled. |
|
Auxiliary Heating Enable |
|
Enables Output on Auxiliary Heating Mask whenever the controller is in Heating Mode. Is off in deadband and cooling. |
|
Auxiliary Heating Output Mask |
|
It indicates the physical output assigned to Auxiliary Heating Output. |
|
Auxiliary Hysteresis |
|
The amount that the heating or cooling requirement must fall before the auxiliary heating or cooling is turned off. [Default 5/255] |
|
Auxiliary Temp (IN-4) - word |
|
Optional Auxiliary Temperature measured on Input #4, smoothed and converted using Input Convert Type and saved in RAM. |
|
Auxiliary Temp (IN-8) – byte |
|
Optional Auxiliary Temperature measured on Input #8 and rounded to single byte value and saved in RAM. |
|
Auxiliary Temp (IN-8) - word |
|
Optional Auxiliary Temperature measured on Input #8, smoothed and converted using Input Convert Type and saved in RAM, 0.01F) |
|
Auxiliary Temp Offset |
|
Number of degrees that zone temperature must exceed active setpoint before auxiliary cooling is brought on. in deg F or deg C [Default 2 F] |
|
Auxiliary Wait Time |
|
The length of time that Auxiliary Temp Offset exists before auxiliary cooling is brought on. [Default 120 s] |
|
Auxiliary Wait Timer |
|
The RAM length of time that Auxiliary Temp Offset exists before auxiliary cooling is brought on. |
|
Baud Rate |
|
The communication speed. 192 = 19,200 baud, 96 = 9600 baud, 12 = 1200 baud. If any other value then baud rate is 9600 baud. New baud rate takes effect immediately. [Default 9600] |
|
Changeover Alarm |
|
If Analog output Changeover HTG/CLG is used, a Changeover alarm is set when an analog output has been assigned to Changeover, and the Changeover Status conflicts with the Control Mode. There is no action taken by the Changeover Alarm. |
|
Changeover Setpoint |
|
Used by Auto Changeover to compare with Water Loop Temperature (IN-7) to decide whether the Changeover Analog Output is Heating or Cooling. |
|
Changeover Status |
|
If Changeover Status is Yes, then the Changeover Analog Output is Heating. If Changeover Status is No, then the Changeover Analog Output is Cooling. |
|
Changeover Mode |
|
Indicates if changeover is Auto or forced via communication message. ChangeoverMode, 0, AutoChangeover; 1 Changeover ON; 2, Changeover Off |
|
CO2 Level |
|
The CO2 level 0-2000 ppm as measured on a sensor on Input 4. A custom Span and Offset has been added for Input 4 |
|
CO2 Ventilation Enable |
|
If CO2 Ventilation Enable is yes, then a Ventilation Minimum Position is calculated based on the CO2 level 0-2000 ppm as measured on a sensor on Input 4. compared to a CO2 Setpoint. |
|
CO2 Ventilation Gain-Ki |
|
A Integral calculation determines the Ventilation Minimum Position. Between Economizer Closed Position, and Economizer Maximum Position. The Ventilation Minimum Position is calculated using a direct-acting Integral algorithm which compares the CO2 Level with the CO2 Ventilation Setpoint, every 30 seconds. If the measured CO2 Level is greater than the CO2 Setpoint, then the Ventilation Minimum Position increases. |
|
CO2 Ventilation Minimum |
|
When the fan is on, if CO2 Ventilation Enable is yes, then the Economizer Cooling Requirement is compared with the Ventilation Minimum Position, and the larger value is used. |
|
CO2 Ventilation Setpoint |
|
The Ventilation Minimum Position is calculated using a direct-acting Integral algorithm which compares the CO2 Level with the CO2 Ventilation Setpoint, every 30 seconds. |
|
Compressor 1 Min On/Off Timer |
|
Times the minimum on and off time for Compressor 1. |
|
Compressor Duty Cycle Time |
|
Time base for duty cycle control of heat pump in 4 s increments [0-1024 s]. [Default: 600 s] |
|
Compressor Duty Cycle Timer |
|
Times the compressor duty cycle. |
|
Compressor Fault Counter |
|
If the Compressor Fault Alarm has been enabled, and the Compressor Fault contacts are closed for a Compressor Fault Delay [Default, 20 s], then the Compressor Fault Alarm is set and the Compressor Fault Counter is incremented. The Compressor Fault Counter is cleared at the beginning of each day. Multiple tries are allowed before the compressor is locked out. If the compressor is locked out, then a Compressor Lockout Alarm is set which must be cleared using communications. If the Compressor Fault Alarm has been enabled, and the Compressor Fault contacts are closed for a Compressor Fault Delay [Default, 20 s], then the Compressor Fault Alarm is set and the Compressor Fault Counter is incremented. The Compressor Fault Counter is cleared at the beginning of each day. |
|
Compressor Fault Delay |
|
If the Compressor Fault contacts are closed for a Compressor Fault Delay [Default, 20 s], then the Compressor Fault Alarm is set. The Compressor Fault Alarm is cleared when the Compressor Fault contacts are open for a Compressor Fault Delay. |
|
Compressor Fault Enable |
|
[Yes, No] If the Compressor Fault Alarm has been enabled, and the Compressor Fault ontacts on input #6 are closed for a Compressor Fault Delay [Default 20 s], then the Compressor Fault Alarm is set and the Compressor Fault Counter is incremented. The Compressor Fault Alarm takes precedence over the Discharge Air Temperature HI/LO Alarm. The Compressor Fault Counter is cleared at the beginning of each day. |
|
Compressor Fault Lockout |
|
If Compressor Fault Lockout is set, and the Compressor Fault Alarm is set, the controller turns OFF compressor. It then retries until Compressor Try Max has been reached. . |
|
Compressor Fault Timer |
|
If the Compressor Fault Alarm has been enabled, and the Compressor Fault contacts are closed for a Compressor Fault Delay [Default, 20 s], then the Compressor Fault Alarm is set and the Compressor Fault Counter is incremented. |
|
Compressor Minimum Off Time |
|
Compressor Minimum Off Time. Minimum compressor off time in 4 s increments [0-1024 s]. |
|
Compressor Minimum On Time |
|
Compressor Minimum On Time. Minimum compressor on time in 4 s increments [0-1024 s]. |
|
Compressor On Timer |
|
Calculates the amount of time compressor stage 1or 2 should be on during the current compressor duty cycle. |
|
Compressor On/Off Mask |
|
The output mask for Comp 1 On/Off output. Always BO-2 . PA_Comp1On-OffMask (T3,31) The output mask assignment for Comp 2 On/Off output. Always BO-2. |
|
Compressor Retry Timer |
|
The controller waits an adjustable Compressor Retry Wait [Default, 120 s] before attempting to restart the compressor. No further action on the compressor output is taken until the Compressor Retry Wait times out. When the Retry Wait times out, if the compressor output is still requested, and if the Compressor Fault Alarm has cleared, then the Compressor Try Counter is incremented. If the Try Counter is less than or equal to the maximum allowed tries, the compressor is restarted. |
|
Compressor Retry Wait |
|
The controller waits an adjustable Compressor Retry Wait [Default, 120 s] before attempting to restart the compressor. |
|
Compressor Run Time Today |
|
Time for Compressor 1 Today in 1/2 minute increments. |
|
Compressor Run Time Total |
|
Accumulated Compressor 1 Run Time in hours. Accumulates from Compressor Run Time Today at midnight. |
|
Compressor Starts Last Hour |
|
Compressor 1 Starts in previous hour . updates from Compressor Starts This Hour at beginning of hour. |
|
Compressor Starts This Hour |
|
Compressor 1 Starts in current hour. |
|
Compressor Starts Today |
|
Compressor 1 Starts Today. |
|
Compressor Starts Total |
|
Accumulated Compressor 1 Starts. Accumulates from Compressor Starts Today at midnight. |
|
Compressor Try Counter |
|
If Compressor Lockout is enabled, and the Compressor Fault Alarm is set, the controller turns OFF compressor. When the Retry Wait times out, if the compressor output is still requested, and if the Compressor Fault Alarm has cleared, then the Compressor Try Counter is incremented. If the Try Counter is less than or equal to the maximum allowed tries, the compressor is restarted. |
|
Compressor Try Max |
|
When the Retry Wait times out, if the compressor output is still requested, and if the Compressor Fault Alarm has cleared, then the Compressor Try Counter is incremented. If the Try Counter is less than or equal to the maximum allowed tries, the compressor is restarted. |
|
Control Mode |
|
The operating modes for the controller are Cooling, Deadband, and Heating. The control enters deadband when the temperature falls one degree F below the Active Cooling Setpoint, or above the Active Heating Setpoint. The control enters cooling when the temperature reaches the Active Cooling Setpoint. The control enters heating when the temperature reaches the Active Heating Setpoint. Shows present mode of the controller. |
|
Control State |
|
Shows present state of the controller. A1_ControlState[UNO,OCC,NSB,MRDY] |
|
Controller Interlock |
|
Shorting input #3 gives Interlock for address (input = 0 V). The interlock is required for all messages with a B4B4h , or B455h destination address. |
|
CLG Temperature Upper Limit |
|
Upper Limit of user adjust in the Digital Display Wall Sensor in the Heating Control Mode. |
|
Cooling Night Setback Temperature SP |
|
This is the desired zone temperature during Night Setback with the controller in cooling mode. |
|
Cooling Occupied Temperature SP |
|
This is the desired zone temperature during an Occupied state in cooling mode. |
|
Cooling Requirement |
|
Cooling calculated value (%) as result of PI algorithm, saved in RAM and used to determine the on time for cooling stages. |
|
Cooling Unoccupied Temperature SP |
|
This is the desired zone temperature during an Unoccupied state with the controller in cooling mode. |
|
Custom Span and Offset |
|
It is possible to configure custom inputs on Inputs 5,6,7, & 8. The Custom Span is the signed difference between the input value at 5 Vdc minus the input value at 0 Vdc. The Custom Offset is the input value at 0 Vdc. [Default, Custom Span = 4095, Custom Offset =, 0] |
|
DAT Compressor Disable |
|
the DAT Compressor Disable is Set, then the Low Discharge Air Temperature Alarm disables the compressor. A High Discharge Alarm does not disable the compressor. |
|
Default Analog Output State |
|
The state assumed by the analog outputs after power reset in personality 0, and the state assumed by the analog outputs during flash downloads. |
|
Default AO State |
|
Default state assumed by Analog Outputs on reset of power in Personality zero, or during Flash programming of the controller. [Default 0] |
|
Default Output State |
|
The state assumed by the binary outputs after power reset in personality 0, and the state assumed by the binary outputs during flash downloads. Bit 0 = OUT 1, … , Bit 7 = OUT 8 [Default 0] |
|
Default Output State |
|
Default state assumed by Binary Ouputs on reset of power in Personality zero, or during Flash programming of the controller. [Default 0] |
|
Demand Group |
|
The Demand Group used by rotating demand shedding. |
|
Demand Reset Range |
|
The maximum Demand Level [Default 6]. |
|
Demand Rotate Level |
|
The Active Demand Level at which rotating demand shedding occurs. |
|
Demand Shed Level |
|
The Active Demand Level at which demand shedding occurs. |
|
Description |
|
A 32 character description may be stored non-volatile memory to help identify that controller. |
|
Device Address |
|
The communications address of the accessed controller. Changing the device address of a controller requires that it be hardware interlocked (see text on the Address Screen to learn how to interlock a controller); address changing should only be done while in Local communications mode, as otherwise multiple controllers addresses may be altered. In Hibyte, Low Byte Order! |
|
Digital Display Enable |
|
Enables the Digital Display Wall Sensor. In deg F/C or in 0.5 deg F/C . |
|
Discharge Air Temp |
|
Optional Discharge Air Temperature measured on Input #6 and rounded to single byte value and saved in RAM. |
|
Discharge Air Temp Alarm Hysteresis |
|
Once a discharge air alarm is set, the temperature must recover by this much before the alarm is cleared. (2-25 F) [Default, 5] |
|
Discharge Air Temp High Limit Alarm Setpoint |
|
The maximum discharge air temperature setpoint. (35-160 F) If the discharge air temperature raises above this point a high discharge air alarm is set.[Default, 140] |
|
Discharge Air Temp Low Limit Alarm Setpoint |
|
The minimum discharge air temperature setpoint. (35-160 F). [Default, 40 F] If the discharge air temperature falls below this point a low discharge air alarm is set. |
|
Discharge Air Temperature SP |
|
Temperature SP for control of Discharge Air Economizer Damper. |
|
Discharge Air Temperature-previous |
|
Previous Discharge Air Temperature measured on Input 8 used for calculating Economizer Cooling Requirement. |
|
Discharge Air Temp-word |
|
Optional Discharge Air Temperature measured on Input #6, smoothed and saved in RAM. 0.01 deg |
|
Economizer Auto Initialize |
|
If Economizer Auto Initialize is Yes, then the Tri-State Economizer output is driven fully closed for an Economizer Base time, every 100 minutes. . [Default No] |
|
Economizer Base Time |
|
The time required to drive the economizer fully open. [Default 120s] |
|
Economizer Close Position SP |
|
The percentage of the Economizer Base Time for the Closed Position. [Default 0] When the economizer is closed it is driven closed for an additional Economizer Base Time. |
|
Economizer Cooling Required |
|
Goes from Economizer Min Position to Max Position SP as the Primary Calculation goes from 0 to 25% |
|
Economizer Damper Close Mask |
|
If Economizer Modulate Enable is set then the output assigned by this mask is used for the tri-state economizer Close Output. [Default Out 7] |
|
Economizer Damper Open Mask |
|
If Economizer Enable is set then the output assigned by this mask is used for On/Off economizer. If Economizer Modulate Enable is set then the output assigned by this mask is used for the tri-state Economizer Open Output. Economizer Modulate Enable takes priority over Economizer Enable. [Default Out 6] |
|
Economizer Freeze Limit Temperature |
|
If the outdoor temperature is less than the Economizer Freeze Limit Setpoint, then the economizer is driven closed. [Default 35] |
|
Economizer Ki |
|
Integral constant used for control of Mixed Air Damper. |
|
Economizer -Kp |
|
Proportional constant used for control of Mixed Air Damper. |
|
Economizer Low Limit Temperature SP |
|
If the outdoor temperature is less than the Economizer Setpoint and greater then the Economizer Low Limit SP, then the economizer is permitted. [Default 45] |
|
Economizer Maximum Position SP |
|
The percentage of the Economizer Base Time for the Maximum Position. [Default 100 %] |
|
Economizer Minimum Position SP |
|
The percentage of the Economizer Base Time for the Minimum Position. [Default 50] |
|
Economizer Offset Temperature |
|
Used by Discharge Air Economizer to determine if Economizer is unable to satisfy the cooling load. If the Cooling Requirement is 100% and the difference between the Zone Temperature and the Active CLG Setpoint is greater than the Economizer Offset Temperature for a Economizer Offset Time, then the Economizer can not satisfy cooling. [Default 2 deg] |
|
Economizer Offset Time |
|
Used by Discharge Air Economizer to determine if Economizer is unable to satisfy the cooling load.. If the Cooling Requirement is 100% and the difference between the Zone Temperature and the Active CLG Setpoint is greater than the Economizer Offset Temperature for a Economizer Offset Time, then the Economizer can not satisfy cooling. [Default 120 seconds] |
|
Economizer Offset Timer |
|
Used by Discharge Air Economizer to time the Economizer Offset Time. |
|
Economizer Position |
|
The actual drive time position of the Tri-state economize in seconds. |
|
Economizer Position SP |
|
The calculated economizer position as fraction of the Economizer Base Time. |
|
Economizer Temperature SP |
|
If the outdoor temperature is less than the Economizer Setpoint and greater than the Economizer Low Limit SP, then the economizer is permitted. |
|
Economizer Timer |
|
Used to determine if Discharge Air Economizer has not been able to satisfy the cooling requirement |
|
Economizer Type |
|
If Economizer Enable is yes then the Economizer Type determines the control sequence. 0 = None, 1= On-Off Economizer, 2 = Modulating Economizer, 3 = Mixed Air Economizer, 4 = Discharge Air Economizer(655A1.2). |
|
Emergency Override |
|
Emergency 1 and Emergency 2 state forces non-volatile memory to turn OFF the fan and electric heat off, and drive economizer closed. |
|
Emergency Status |
|
RAM Emergency Status 0 = indicates that no emergency is present; 1 = emergency 1 state is set; 2 = emergency 2 state is set. |
|
Factory Analog Input Tolerance |
|
Tolerance used to test Analog Inputs during Factory Test. Not a User Parameter. |
|
Factory Analog Output Tolerance |
|
Tolerance used to test Analog Outputs during Factory Test. Not a User Parameter. |
|
Factory Default Table |
|
Type "Table 1" <Enter> This causes a "Brain Dump" of the standard Factory Default Table 1. This command requires a Controller Interlock. |
|
Fan On/Off Mask |
|
The output mask assignment for fan output. Always BO-1. |
|
Fan Proof Delay |
|
Proof of Fan Delay, Table 3, Entry 18 [10s], Wait on start, and debounce 10 s |
|
Fan Proof Enable |
|
A Proof of Fan Switch across Input 7 (Water loop) Opens on proof of fan. If Proof of Fan Enable is Yes, the switch is examined whenever the fan, or high fan is on, or in Heating with Gas Heat Enable = Yes. The Proof of Fan Switch is for information only. No actions result from proof of fan alarm. |
|
Fan Proof Status |
|
Proof of Fan Status set when proof of fan established. |
|
Fan Run Time Today |
|
Time for Fan Run Today in 15 minute increments. |
|
Fan Run Time Total |
|
Accumulated Fan Run Time in hours. Accumulates from Fan Run Today at midnight. |
|
Fan Start Delay |
|
Adds Fan Start Delay (0..255s) on Reset of Power and change of Control State. Fan does not start until Fan Start Timer counts to zero. For Constant Fan this delays the initial start after reset or schedule change. The Intermittent Fan does not start until controller leaves deadband which is typically more than 30 seconds after reset or schedule change and Fan Start Delay should be greater than 30 seconds. See also Fan Start Timer |
|
Fan Start Timer |
|
On Reset of Power and change of Control State Fan does not start until Fan Start Timer counts to zero. For Constant Fan this delays the initial start after reset or schedule change. The Intermittent Fan does not start until controller leaves deadband which is typically more than 30 seconds after reset or schedule change and Fan Start Delay should be greater than 30 seconds. See also Fan Start Delay. |
|
Fan Wait Time |
|
Delay time for fan to turn off after entering Deadband. [Default, 30] Time for fan to run at end of compressor cycle with intermittent fan operation. [0-255 s]. [Default, 30 s] |
|
Flash Enable |
|
Enables update of firmware (executable application program) over RS-485 communication. [Default: No] |
|
Gas Heat Enable |
|
A new option that overrides fan operation for gas heat for AC personalities1,2,3,4 only. In Heating Mode the fan does not come on . When Gas heat is used the Fan is controlled by the Heat stage. |
|
Group Address |
|
This specifies the Group Address (Group Address 0) to which the controller will respond. Default 512D (200H) Range 0x0100-0xFF00 (multiples of 0x100) Resolution 256 |
|
Half Degree Enable |
|
Enables temperature control in 0.5 deg F/C. |
|
Heat 1 Mask |
|
It indicates the physical output assigned to Heat 1 Output for AC personalities or RV output for Heat Pump Personalities. Always BO-4. Read Only. |
|
Heat 2 Mask |
|
It indicates the physical output assigned to Heat 2. |
|
Heat Base Time |
|
This represents the duty cycle to be used for electric/gas heat applications. 4 sec increments. Default:60*4 seconds Range: 0-255 seconds Resolution: 4 second |
|
Heat Base Timer |
|
Times the heating duty cycle for Heat 1 and Heat 2. PA_HeatBaseTimer (T10,55,Byte) |
|
Heat Fan Delay Enable |
|
If Heat Fan Delay Enable is yes in heating mode, Intermittent Fan does not come on until Heating Requirement > 0. Fan stays on as heat duty cycles in heating mode. |
|
Heat Min Off Time |
|
This represents the Minimum off time to be used for heat applications. 4 sec increments. Default:60*4 seconds |
|
Heat Min On-Off Timer |
|
Times the minimum on and off time for Heat 1, and times the minimum on and off time for Heat 2. |
|
Heat Min OnTime |
|
This represents the Minimum on time to be used for heat applications. 4 sec increments. Default:60*4 seconds. |
|
Heat On Timer |
|
Calculates the amount of time Heat 1 should be on during the current Heating Base Time, and calculates the amount of time Heat 2 should be on during the current Heating Base Time |
|
Heat Pump Compressor Enable |
|
This RAM flag is set to True at power up. When set the HP Compressors operate under normal sequence control. It can be cleared Only with MT=10, M1 = 12 Heat Pump Disable, and set only with MT=10, M1 =11 Heat Pump Enable Message. If cleared the Heat Pump compressor is locked out. Included for backward compatibility. |
|
Heat Pump Request |
|
This RAM flag is set to True when Water Source Heat Pumps request heating or cooling operation. It is included for backward compatibility. |
|
Heating Night Setback Temperature SP |
|
This is the desired zone temperature during Night Setback with the controller in heating mode. |
|
Heating Occupied Temperature SP |
|
Occupied Heating Temperature Setpoint This is the desired zone temperature during an Occupied state in heating mode |
|
Heating Requirement |
|
Heating calculated value (%) as result of PI algorithm, saved in RAM and used to determine the on time for heating stages. |
|
Heating Unoccupied Temperature SP |
|
Unoccupied Heating Temperature Setpoint This is the desired zone temperature during an Unoccupied state with the controller in heating mode. |
|
HTG Temperature Lower Limit |
|
Lower Limit of user adjust in the Digital Display Wall Sensor in the HTG Control Mode. In deg F/C or in 0.5 deg F/C. |
|
High Fan CLG Enable |
|
The switching between low speed and high-speed fan may be enabled for cooling mode. [Default No] |
|
High Fan Delay Time |
|
If enabled, and if the zone temperature deviates from the active control setpoint by the High Fan Temperature Offset for at least the High Fan Delay Time, then the high-speed fan output replaces the low-speed fan. [Default 30s] |
|
High Fan Delay Timer |
|
Used to time when the zone temperature deviates from the active control setpoint by the High Fan Temperature Offset [RAM sec] |
|
High Fan HTG Enable |
|
The switching between low speed and high-speed fan may be enabled for heating mode . [Default No] |
|
High Fan Only CLG Enable |
|
The high-speed fan only may be forced for cooling mode and deadband entered from cooling. [Default No] |
|
High Fan Only HTG Enable |
|
The high-speed fan only may be forced for heating mode and deadband entered from heating. [Default No] |
|
High Fan Output Mask |
|
The High Fan output is used to change fan speed when the zone temperature is outside the setpoint by the High Fan Temperature Offset for a High Fan Delay Time. In switching between High & Low we want to make for 1 second before break. |
|
High Fan Temperature Offset |
|
If enabled, and if the zone temperature deviates from the active control setpoint by the High Fan Temperature Offset for at least the High Fan Delay Time, then the high-speed fan output replaces the low-speed fan. Control is switched back to the low-speed fan when zone temperature has returned to the active control setpoint for High Fan Delay Time. |
|
Holiday Status |
|
Indicates that today is a holiday. |
|
Ignore Globals Enable |
|
If set to [Yes], all commands on the communications line sent using global addressing are ignored. [Yes, No Default No]. |
|
Input Raw |